Skip to content
Threat Brief

← All advisories

CVE-2021-22681

Critical 9.8KEV · exploitedFix status unknown

Rockwell Multiple Products Insufficient Protected Credentials Vulnerability

Record last updated

CVSS score

9.8

Critical on a 0 to 10 scale

EPSS, chance of exploitation in 30 days

64%

Higher than 99% of scored CVEs. A prediction, not evidence.

CISA remediation deadline

240days overdue

Passed 240 days ago for U.S. federal agencies

Description

Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800.

Weakness: CWE-522

Patching and mitigation

Patch status
Unknown: no source documents a fix
Mitigation
None documented
Vendor guidance
support.rockwellautomation.com (opens in a new tab)

Affected products

VendorProductAffected versionsFixed inPer
RockwellMultiple ProductsNot documentedNot documentedCISA KEV

Timeline

  1. Disclosure

    CVE record published by icscert

    Source: CVE Program (opens in a new tab)

  2. 05 Mar 2026KEV

    Added to the CISA Known Exploited Vulnerabilities catalog

    Source: CISA KEV (opens in a new tab)

  3. 05 Mar 2026Exploitation

    Exploitation confirmed by CISA KEV

    Source: CISA KEV (opens in a new tab)

Vendor guidance and references